Estimation of voltage dependent load models through power and frequency measurements

A. Ortega, F. Milano

IEEE Transactions on Power Systems Vol. 35, nº. 4, pp. 3308 - 3311

Summary:
This letter proposes an optimization-free technique to estimate the parameters of voltage dependent loads through the measurements of only the load active and reactive power consumption and frequency deviations at the load bus. The technique is shown to be a relevant consequence of the dependency of power flow equations on the bus voltage phase angles. The WSCC 9-bus and the IEEE 14-bus systems serve to illustrate the proposed technique.


Keywords: Voltage dependent load, state estimation, frequency measurement, frequency divider, phasor measurement unit (PMU).


JCR Impact Factor and WoS quartile: 6,663 - Q1 (2020); 6,600 - Q1 (2022)

DOI reference: DOI icon https://doi.org/10.1109/TPWRS.2020.2987259

Published on paper: July 2020.

Published on-line: April 2020.



Citation:
A. Ortega, F. Milano, Estimation of voltage dependent load models through power and frequency measurements. IEEE Transactions on Power Systems. Vol. 35, nº. 4, pp. 3308 - 3311, July 2020. [Online: April 2020]